Översyn av skyddsanordning samt nollpunkt för fördelningsstationen Fs Myrängen

University essay from KTH/Elektroteknisk teori och konstruktion

Author: Amr Elawa; [2014]

Keywords: ;

Abstract: This is a report of a Master’s thesis done in behalf of the local network in Stockholm, under Fortum Distribution AB. The thesis was to conduct a review of a distribution station named Fs Myrängen located in Täby. A model was created for the 11 kV network linked to the secondary side of Fs Myrängen. Based on this model and using symmetrical components, theoretical fault currents (short circuit and ground fault) could be calculated. The results of these fault currents are used to investigate and develop new settings for relay protection and ground equipment in the station. The results of the calculated fault currents were also used to investigate unwanted voltages that occurs for grounded parts due to earth faults. The value of these unwanted voltages was then compared to heavy current regulations developed by the Electrical Safety Authority in Sweden. Another element of the work was to create a rehabilitation plan for the structure on the 11 kV side of Fs Myrängen, the main goal regarding the rehabilitation plan was to investigate the advantages and disadvantages that exist at a possible transition to numerical protection relays. This was done by making a market overview of the different types of numerical protection relays and compare these with the existing analog protective device in Fs Myrängen. The study showed that protective relay settings should be revised according to the recommendations in the report, ground equipment should be replaced with a self-regulating type, transformers should be replaced due to age and capacity limitations. Regarding a switch to numerical protection relays the type REF615 from ABB was recommended, in that case the control board in the station should be replaced to a station computer. Furthermore should current transformers be replaced to recive a desired sensitivity regarding detection of ground faults. The report also showed that Fs Myrängen meets the regulations of unwanted voltages over grounded parts in distribution stations due to earth faults.

  AT THIS PAGE YOU CAN DOWNLOAD THE WHOLE ESSAY. (follow the link to the next page)